l Purpose
This product is an emergency protective equipment necessary for occasions where it comes into contact with acids, alkalis, organics and other toxic and corrosive substances. In the event of an accident, the damage can be reduced to a minimum through rapid showering and washing.
l Main performance parameters
Pressure rating MPa
|
Flow L/min
|
Applicable conditions
|
Nominal pressure
|
Sealing pressure
|
Work pressure
|
Spray
|
Wash your eyes
|
Water meets sanitary standards at room temperature
|
0.4
|
0.45
|
0 . 20 ~ of 0. The 40
|
≥ 75. 5
|
≥ 11.4
|
l Structure (with photos)
- Use ball valve and spiral seal structure to control spraying and washing eyes.Easy to operate, fast opening and closing, and reliable sealing.
- Theeyewash pipeline is equipped with a water seepage hole, which can empty the residual water in the eyewash nozzle, which is conducive to the cleaning and sanitation of the pipeline and anti-freezing.
l Main material : high quality 304 stainless steel
l Surface treatment : epoxy resin spray treatment on the surface
l Installation and adjustment again:
- Theproduct model, certificate, instruction manual, and packing list must be re-checked before installation.
- Theinstallation location should bewithin 15 meters of the accident-prone place , and the flushing place can be reached within 10 seconds at a running speed .
- Installation and debugging:
- Thebase is connected with the lower half of the riser: the raw material tape is wound around the base thread and the water outlet is screwed tightly.
- Install the base: adjust the direction of the three-way drain according to the position of the drainage pipe, mark the hole position according to the screw hole of the base, and then set theM 10 expansion screw or anchor bolt according to the ground level .
- Install the flushing pipeline: screw the shower nozzle on the elbow of the nozzle tube, and then wrap the raw material tape around the other thread of the nozzle tube, connect it to the upper part, adjust the position, and lock it with a locking nut .
- Connect the upper part and the lower part: put the cushion in the place of the female, and tighten the female.
- Install the eyewash basin part: Wrap the raw material tape around the thread of the nozzle of the eyewash basin, and tighten it with the lower half of the reducing tee connection;
- Install the eyewash dual nozzle part:put a G ½ ” mesh pad in the lock nut , and connect it with the G ½ ” tube and screw it tightly.
- Connect the water inlet and drain pipes, try to install the push plate, insert the push plate into the valve stem of the eyewash valve, turn the push plate counterclockwise to make the valve in the closed position, remove the push plate, re-install and adjust the direction of the push plate , Make the front of the push plate upright and open repeatedly to check whether the valve switch is in place flexibly and whether there is jamming.
l Tips for use :
1 . This product 0 environments than ℃, if 0 or less ℃ using antifreeze required for maintenance of the pipeline;
- Before installation, please rinse the water inlet pipe clean in advance;
- It is recommended to install a water inlet control valve in the water inlet pipe. After use, close the water inlet control valve first, and then close the eyewash valve after the water in the main body is drained.
l How to use
Before use, open the water inlet control valve
- Whenshowering is needed, pull down the shower switch handle to open the shower valve (opening angle90 °), push up the shower switch handle, and the shower valve closes (the ball valve connecting rod is closed at 45 ° above the ball valve . 45 ° below is the open state).
- If you need to wash your eyes, please push the eyewash switch push plate clockwise to open the eyewash valve, and pull back the push plate counterclockwise to close the eyewash valve.The dust cover needs to be reset after use.
l Maintenance
1 . Only allowed emergency use when the accident occurred, the development system to do bathing is strictly prohibited, to avoid product failure, resulting in undue accident.
- Comprehensive inspections should be carried out more than once a week to check the reliability and effectiveness of the device to ensure emergency and effective use in the event of an accident.This product is not a medical device, it only serves as an emergency shower and reduces the damage of harmful substances to the human body.
- In theevent of an accident, the victim must choose the shower time according to the degree of infringement of harmful substances.Prepare emergency rescue measures during the period.
l Simple troubleshooting
Serial number
|
Therefore, failure
|
cause
|
elimination method
|
1
|
Small flow of flushing water
|
Inlet water pressure and pipe diameter are small, and the flow is not enough
|
Adjust the inlet water pressure and inlet pipe diameter
|
2
|
Little water output from eyewash
|
a. The water inlet filter of the eyewash dual nozzles is blocked
b. The eye wash valve sealing rubber pad falls off
|
a. Unscrew the dual nozzles and clean the filter
b. Remove the eyewash valve, apply anaerobic glue on the connecting rubber pad screw and screw it firmly
|
3
|
The eyewash valve is not closed tightly
|
Damaged eye wash valve sealing rubber gasket
|
Remove the eyewash valve and replace the rubber pad
|
4
|
Lots of water in the eyewash basin
|
The drainage hole in the eyewash basin is blocked or the sewer pipe is blocked
|
Eliminate blockages
|
Packing List
After unpacking, please count the number of accessories according to the following list and check whether there is any transportation damage. If there is any problem or insufficient quantity, please contact our company’s local distributor or our company immediately, and you will get a satisfactory answer.
Parts list
Serial number
|
Part name
|
Quantity
|
1
|
Shower nozzle
|
1 set
|
2
|
Nozzle tube
|
1 set
|
3
|
Upper half
|
1 set
|
4
|
Bottom half
|
1 set
|
5
|
Base
|
1 piece
|
6
|
Eyewash basin part
|
1 set
|
7
|
Eyewash double nozzle part (with filter mesh rubber pad)
|
1 set
|
8
|
Shower switch handle
|
1 set
|
9
|
Eyewash switch push plate
|
1 piece
|
10
|
Spare parts
|