Eye Wash Station Safety Information

  • Home
  • ANSI Z358.1 standard
  • Eye Wash Station Safety Information
The Effect of Long-Term Use of an Eyewash Solution on the Ocular Surface Mucin Layer
March 29, 2022
stainless steel eye washe
If you get something from the lab in your eye— Run some water through the eyewash fountain before you use it. Retract
May 1, 2022

Eye Wash Station Safety Information

Categories
  • ANSI Z358.1 standard
  • Company news
  • Technical news
Tags

The first 10 to 15 seconds after exposure to a hazardous substance, especially a corrosive substance, are
critical. Delaying treatment, even for a few seconds, may cause serious injury. Emergency showers and
eyewash stations provide on‐the‐spot decontamination. They allow workers to flush away hazardous
substances that can cause injury. Accidental chemical exposures can still occur even with good
engineering controls and safety precautions. As a result, it is essential to look beyond the use of goggles,
face shields, and procedures for using personal protective equipment. Emergency showers and eyewash
stations are a necessary backup to minimize the effects of accident exposure to chemicals. Emergency
showers can also be used effectively in extinguishing clothing fires or for flushing contaminants off
clothing.
Currently there is no standard for the design or placement of eyewash stations or emergency showers.
As a result, the American National Standards Institute (ANSI) Standard Z358.1‐2009 “Emergency
Eyewash and Shower Equipment” is generally used as a guide.
For emergency showers and eyewash stations to be effective, the American National Standards Institute
(ANSI) Standard for Emergency Eyewash and Shower Equipment (ANSI Z358.1‐2009) recommends that
the affected body part must be flushed immediately and thoroughly for at least 15 minutes using a large
supply of clean fluid under low pressure. Water does not neutralize contaminants ‐‐ it only dilutes and
washes them away. This fact is why large amounts of water are needed. However, other references
recommend a minimum 20‐minute flushing period if the nature of the contaminant is not known. The
flushing or rinsing time can be modified if the identity and properties of the chemical are known. For
example:
•a minimum 5‐minute flushing time is recommended for mildly irritating chemicals,
•at least 20 minutes for moderate‐to‐severe irritants,
•20 minutes for non‐penetrating corrosives, and
•at least 60 minutes for penetrating corrosives.
Non‐penetrating corrosives are chemicals which react with human tissue to form a protective layer
which limits the extent of damage. Most acids are non‐penetrating corrosives. Penetrating corrosives,
such as most alkalies, hydrofluoric acid and phenol, enter the skin or eyes deeply. Penetrating corrosives
require longer water flushing (a minimum of 60 minutes) than non‐penetrating corrosives (a minimum
of 20 minutes). In all cases, if irritation persists, repeat the flushing procedure. It is important to get
medical attention as soon as possible after first aid has been given. A physician familiar with procedures
for treating chemical contamination of the eyes and body should be consulted.
To be effective, the equipment has to be accessible. ANSI recommends that a person be able to reach
the equipment in no more than 10 seconds. Other recommendations include that the emergency
shower or eyewash station should:
•be located as close to the hazard as possible
•not be separated by a partition from the hazardous work area.
•be on an unobstructed path between the workstation and the hazard. (Workers should not have to
pass through doorways or weave through machinery or other obstacles to reach them.)
•be located where workers can easily see them ‐ preferably in a normal traffic pattern.
•be on the same floor as the hazard (no stairs to travel between the workstation and the emergency
equipment)
•be located near an emergency exit where possible so that any responding emergency response
personnel can reach the victim easily.
•be located in an area where further contamination will not occur
•provide a drainage system for the excess water (remember that the water may be considered a
hazardous waste and special regulations may apply).
•not come into contact with any electrical equipment that may become a hazard when wet, and
•be protected from freezing when installing emergency equipment outdoors.
Work areas and operations that may require these devices include:
•battery charging areas,
•laboratories,
•spraying operations,
•high dust areas,
•dipping operations, and
•hazardous substances dispensing areas.
One person in the work area should be designated responsible for inspecting and operating (activating)
the emergency shower, eyewash station, combination units, and drench hoses weekly. A weekly check
will make sure that there is flushing fluid available as well as clear the supply line of sediments and
minimize microbial contamination caused by ‘still’ or sitting water. This person should keep a signed,
dated record. The ANSI standard also recommends a complete inspection on an annual (yearly) basis.
Preventive maintenance inspections should be done every six months to check for such problems as
valve leakage, clogged openings and lines, and adequacy of the fluid volume. A work record of these
inspections should be kept. Replacement parts should be kept on hand to prevent the system from
becoming non‐functional. If the system breaks down for any reason, the workers in the area should be
properly warned and protected.
Personal eyewash equipment should be inspected and maintained according to the manufacturer’s
instructions and at least annually for overall operation.

Share
admin
admin

Related posts

Heat-Traced Safety Stations

March 14, 2023

Is it better to heat the eyewash station or not to heat it? heat tracing Safety eyewash and Showers.


Read more
March 13, 2023

Lab Drying Rack Pegboard Bench-top – Wall-Mount- Cleaning Glassware


Read more
Lab Fume Exhaust

Lab Fume Exhaust

March 12, 2023

How to Choose the Right Lab Fume Exhaust?


Read more
March 8, 2023

What Kind Of Shower safety equipment Flushing Fluid Can Be Used?


Read more
February 27, 2023

Laboratory Extraction Arms,Flexible Arm,Fume Extractor Arm?


Read more
February 14, 2023

Emergency Combination Shower with Eyewash Station for hemical plant


Read more

Comments are closed.

  • Bench Eye Wash
  • Combination Shower & Eye Wash
  • Multi-function Eye Wash Station
  • Portable Eye Wash
  • Wall Mounted Eye Wash
  • Eye Wash Fittings
  • Lab Tap
  • PP Sink
  • Fume Extractor
  • PP Pegboard
  • Water Gas Valve
  • Lab Fittings
  • Other Products
    Contact
    Address: Industrial District,Wuqiang county ,Hebei province,China
    Tel: +86-318-3832252,+86-318-3832163
    Fax:+86-318-382 1299
    E-mail: rwd2016@163.com
Skype :cnchinawujie
Sitemap

Translation

EnglishالعربيةবাংলাFrançaisDeutschΕλληνικάBahasa IndonesiaItalianoBahasa MelayuپارسیPortuguêsРусскийSlovenčinaEspañolSvenskaภาษาไทยTiếng Việt

RunWangDa company

Is a professional enterprise concentrating on R&D, manufacture of modern laboratory fittings and eyewash.As the first manufacturer of domestic laboratory accessories, our main products include : Eye wash (Station),Emergency Shower, laboratory faucets for water and gas, fume exhaust, peg board, PP sink, emergency shower ,etc.We only produce the best quality eye wash and Laboratory Service Fittings! Classic Version
Runwangda for your Safety, Lab and Science Laboratory

LAST UPDATE

  • heat tracing Safety eyewash and Showers Drawing PDF
    March 14, 2023
  • Is it better to heat the eyewash station or not to heat it? heat tracing Safety eyewash and Showers.
    March 14, 2023
  • Lab Drying Rack Pegboard Bench-top – Wall-Mount- Cleaning Glassware
    March 13, 2023
© 2017 Hebei Runwangda Making Clean Materials Co., Ltd. All Rights Reserved.