l Purpose
This product is an emergency protective equipment necessary for occasions where it comes into contact with acids, alkalis, organics and other toxic and corrosive substances. In the event of an accident, the damage can be reduced to a minimum through rapid showering and washing.
l Main performance parameters
Pressure rating MPa
|
Flow L/min
|
Applicable conditions
|
Nominal pressure
|
Sealing pressure
|
Work pressure
|
Spray
|
Wash your eyes
|
Water meets sanitary standards at room temperature
|
0.4
|
0.45
|
0 . 20 ~ of 0. The 40
|
≥ 75. 5
|
≥ 11.4
|
l Structure (with photos)
- Use ball valve and spiral seal structure to control spraying and washing eyes. Easy to operate, fast opening and closing, and reliable sealing.
- There is a flow regulating valve to control the eyewash flow, which can be adjusted by itself (for the adjustment method, see installation and debugging).
- Theeyewash pipeline is equipped with a water seepage hole, which can drain the residual water in the eyewash nozzle, which is conducive to the cleanliness and antifreeze of the pipeline (part of the water is discharged into the sewer pipe through the hole when the eye is washed, which does not affect the use effect)
l Main material : high quality stainless steel
l Installation and adjustment again:
- Theproduct model, certificate, instruction manual, and packing list must be re-checked before installation.
- Theinstallation location should bewithin 15 meters of the accident-prone place , and the flushing place can be reached within 10 seconds at a running speed .
- Installation and debugging:
- Thebase is connected with the lower half of the riser: the raw material tape is wound around the base thread and the water outlet is screwed tightly.
- Install the base: adjust the direction of the three-way drain according to the position of the drainage pipe, mark the hole position according to the screw hole of the base, and then set theM 10 expansion screw or anchor bolt according to the ground level .
- Install the shower pipeline: screw the shower nozzle tightly on the elbow of the nozzle tube (thethread is wrapped around the raw material tape ), and then wrap the raw material tape on the other thread of the nozzle tube, connect it with the upper half, and adjust it. Position, lock with a locking female.
- Connect the upper part and the lower part: put the cushion in the place of the female, and tighten the female.
- Install the eyewash basin part: Wrap the raw material tape around the thread of the nozzle of the eyewash basin, and tighten it with the lower half of the reducing tee connection;
- Install the eyewash dual nozzle part:put a G ½ ” mesh pad in the lock nut , and connect it with the G ½ ” tube and screw it tightly.
- Connect the water inlet and drain pipes, try to install the push plate, insert the push plate into the valve stem of the eyewash valve, turn the push plate counterclockwise to make the valve in the closed position, remove the push plate, re-install and debug the push plate Direction, make the front of the push plate straight up, open repeatedly, check whether the valve switch is in place flexibly and whether there is jamming.
- The adjustment method of the flow control valve: the middle of the two pipes of the double nozzle is the flow control valve.It has been debugged before leaving the factory. However, due to the difference in water supply pressure and flow, it can be re-adjusted on site during installation to adjust the flow to human eyes. Adjustment method : Take off the top protective cap, adjust the valve stem with a flat-blade screwdriver, and rotate it clockwise to reduce the flow rate. Turn counterclockwise to increase the flow rate.
l Tips for use :
- This product is used in anenvironment above 0 ℃, if it is used below 0 ℃, pipeline antifreeze maintenance is required;
- Before installation, please rinse the water inlet pipe clean in advance;
- It is recommended to install a water inlet control valve in the water inlet pipe. After use, close the water inlet control valve first, and then close the eyewash valve after the water in the main body is drained.
l How to use
Before use, open the water inlet control valve
- Whenshowering is needed, pull down the shower switch handle to open the shower valve (opening angle90 °), push up the shower switch handle, and the shower valve closes (the ball valve connecting rod is closed at 45 ° above the ball valve . 45 ° below is the open state).
- If you need to wash your eyes, please push the eyewash switch push plate clockwise to open the eyewash valve, and pull back the push plate counterclockwise to close the eyewash valve.The dust cover needs to be reset after use.
l Maintenance
- Only allow emergency use when an accident occurs. It is strictly forbidden to use it in bathing. Rules and regulations and inspections should be stipulated to prevent violations or regular bathing and hand washing appliances, which may cause product failure and cause undesirable accidents.
- Comprehensive inspections should be carried out more than once a week to check the reliability and effectiveness of the device, to ensure emergency and effective use in the event of an accident, and to reliably provide personal safety and health protection.This product is not a medical device, it only serves as an emergency shower and reduces the damage of harmful substances to the human body.
- In theevent of an accident, the victim must choose the shower time according to the degree of infringement of harmful substances.Prepare emergency rescue measures during the period.
l Simple troubleshooting
Serial number
|
Common malfunctions
|
cause
|
elimination method
|
1
|
Small flow of flushing water
|
a. The inlet water pressure and pipe diameter are small, and the flow is not enough
|
a Adjust the inlet water pressure and inlet pipe diameter
|
2
|
Little water output from eyewash
|
a. The water inlet filter of the eyewash dual nozzles is blocked
b. The valve stem of the flow control valve is adjusted excessively
|
a. Unscrew the dual nozzles and clean the filter
b. Rotate the control valve stem counterclockwise
|
3
|
Lots of water in the eyewash basin
|
The drainage hole in the eyewash basin is blocked or the sewer pipe is blocked
|
Eliminate blockages
|
l Packing list
Serial number
|
Part name
|
Quantity
|
1
|
Shower nozzle
|
1 set
|
2
|
Nozzle tube
|
1 set
|
3
|
Upper half
|
1 set
|
4
|
Bottom half
|
1 set
|
5
|
Base
|
1 piece
|
6
|
Eyewash basin part
|
1 set
|
7
|
Eyewash double nozzle part (with filter mesh rubber pad)
|
1 set
|
8
|
Shower switch handle
|
1 set
|
9
|
Eyewash switch push plate
|
1 piece
|
10
|
Spare parts
|